Engine
| Problem | Items to Check, Troubleshooting Steps, Remedies |
|---|---|
|
Engine will not turn over
|
Low voltage possible causes:
Check the starter signal and ECM fuses in the 24 VDC distribution panel. (Position 16 & 9). Check the starter motor relay (Position 35). Replace or recharge the batteries or jump start / boost the batteries to start the engine (refer to Jump Start the VPS800A-T4). |
|
Unsuccessful start attempts / Engine cranks but fails to start |
If the generator controller has performed all three consecutive start attempts and has detected that the engine has not started, the ‘Fail to Start’ shutdown alarm message will be displayed. Possible causes:
Possible remedies:
NOTE Ensure that the gasket is installed on the fuel filters.
|
|
Engine requires multiple cranking attempts before starting |
Check that the fuel system is primed according to the engine manufacturer’s requirements. Check that all fuel lines, fittings and fuel filters are secure and that they do not allow air to enter the fuel system. |
Possible causes: